Input |
|
Rating |
Voltage |
Frequency |
Voltage range |
Power Factor |
THDi |
|
1000 VA |
220V, 230V, 240V, 1Ø 2Wires |
40 to 70 Hz |
176-300 VAC at 100% load, 110-300 VAC at 50% load |
>99% |
≤3% |
|
|
|
Output |
|
Active Power cosφ=1 |
Voltage (on battery) |
Frequency (on battery) |
Transfer Time |
UPS Design Technology |
Output Wave Form |
Total Harmonic distortion (THD) |
Crest Factor |
|
1000W |
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires |
50/60 Hz +/-0.1% |
0 ms |
Online double conversion design |
Pure Sinewave |
≤2% (linear load), ≤4% (non linear load) |
3:1 |
|
|
|
|
|
Protection |
|
Overload Protection |
Short Circuit Protection |
|
110% for 10min, 130% for 1min, >130% for 3sec |
UPS output cut off immediately using input fuse/circuit breaker protection |
|
|
|
System Display |
|
|
UPS status, load level, battery level, input/output voltage, discharge time and fault indicators |
|
|
|
Alarm |
|
Battery mode |
Low battery |
Overload |
Fault |
|
Sounding every 4 second |
Sounding every second |
Sounding twice every second |
Continuously beeping |
|
|
|
Battery |
|
Battery Type |
Typical Recharge Time |
Charging Current |
DC Voltage |
Extended Back up time |
|
12V 7Ah |
4 hours to 90% capacity |
1.5A |
36 VDC |
10~15 min depending on load |
|
|
|
Communication |
|
USB, RS-232, AS-400** |
SNMP** |
Compatibility |
|
Interface with power management software |
Power Management from SNMP manager and web browser |
Supports Windows family, Linux, Unix and Mac |
|
|
|
Physical |
|
W x D x H mm |
Net Weight Kgs |
|
|
|
|
Environment |
|
Ambient operation |
Audible noise |
|
Maximum elevation at 1000m, 0 to 40°C, 20 to 95% humidity (non-condensing) |
<50dBA at 1 Meter |
|
|
|
Standards
& Certifications |
|
Performance |
Safety |
EMC (EMS / EMI) |
Design, production, & services |
Environment |
Marking & Certifications |
|
EN50091-3/IEC 62040-3 |
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950 |
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22,
EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B - |
ISO 9001 |
ISO 14001 certified company |
CE, TUV/GS, UL, cUL, c-Tick |
|
|
*In LV system, only 12V/7Ah x 3 for 1K model and 12V/7Ah x 6 for 3K model are available.
NOTE 1: Derate to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
NOTE 2: If the UPS is installed or used in a place where the altitude is above than the rated altitude, the output power must be derated one percent per 100m.
NOTE 3: For Long run models (6kVA~10kVA), When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating x N/20
** For optional features
***Product specifications are subject to change without further notice |